Who Knew 11,000 Volts is Only ‘Medium Voltage?’

Roland | May 22, 2008 at 8:58 am | In Photos, Technical, Latest News |

Blog Board member and chief electrician Ed van Weijen sent us this photo and technical description of the 11,000-volt main switchboards on board Eurodam.

One of the main switchboard’s 11,000-volt bus-bars, located inside the switchboard.

GENERAL:
On the Eurodam the 11,000-volt switchboard is built out of two separate switchboards, the aft and forward switchboards, which are installed in two separate rooms connected by one interconnecting line called a bus tie.

The remote control of these two MSWB’s is handled by the ship automation system (IAS) with the direct supervision of the power management system (PMS).

FORWARD MAIN SWITCHBOARD XA/872A:
Three generators provide the supply for this switchboard (FWD MSBD).

The FWD MSBD supplies the following users:

107 Bus-tie with AFT MSBD

133 Spare main transformer FZ/003TFC

121 Propulsion transformer FZ/001TFA (portside, half motor)

131 Forward main transformer FZ/003TFA

123 Propulsion transformer FZ/001TFC (starboard, half motor)

161 Bow thruster, 1900KW YA/764A

163 Bow thruster, 1900KW YA/764C

151 AC-compressor, 1060KW YB/685A

153 AC-compressor, 1060KW YB/685C

141 Accommodation substation MFZ6 transformer, FZ/004TFF

143 Accommodation substation MFZ5 transformer, FZ/004TFB

145 Accommodation substation MFZ4 transformer, FZ/004TFD

AFT MAIN SWITCHBOARD XA/872B:
Three generators provide the supply for this switchboard (AFT MSBD).

The AFT MSBD supplies the following users:

208 Bus-tie with FWD MSBD

234 Spare main transformer FZ/003TFC

224 Propulsion transformers FZ/001TFD (starboard, half motor)

232 Aft main transformers FZ/003TFB

222 Propulsion transformers FZ/001TFB (portside, half motor)

262 Bow thruster, 1900KW YA/764B

254 AC-compressor, 1060KW YB/685D

252 AC-compressor, 1060KW YB/685B

246 Accommodation substation MFZ1 transformers, FZ/004TFA

244 Accommodation substation MFZ2 transformer, FZ/004TFE

242 Accommodation substation MFZ3 transformer, FZ/004TFC

248 Galley transformer FZ/004TFG

No Comments yet »

RSS feed for comments on this post. TrackBack URI

Leave a comment

Comments are moderated. The topic of this site is exclusively Eurodam. Everything else is off-topic. No profanity or harsh rhetoric, please.

You must be logged in to post a comment.

Powered by WordPress with Pool theme design by Borja Fernandez.
Entries and comments feeds. Valid XHTML and CSS. ^Top^